Recorded value
Industrial Redundancy: partial
Evidence
- supportsenbitcon.deVendor websitesCorroborated sourcehttps://www.enbitcon.de/media/d1/91/4b/1722343329/SNS-EN-SNi20-Datasheet.pdf
The SNi20 datasheet lists 'Intrusion detection and prevention' among its protections and 'Vulnerability detection (option)' as an add-on, over a deep-packet-inspection list that covers Modbus, UMAS, S7, EtherNet/IP, CIP, OPC UA, BACnet/IP, PROFINET, IEC 60870-5-104 and IEC 61850. Limited rather than native because the datasheet names intrusion prevention and vulnerability detection but no signature feed for known flaws in industrial equipment. For redundancy the datasheet's own REDUNDANCY heading gives only 'Bypass (safety mode)', and its safety mode covers 'cluster, bypass and power supply' — no industrial ring protocol.
Retrieved 5 Nov 2026
History
Correcting a value records the new one and dates the old one — nothing is overwritten, so you can see what this page said before, and when it changed.
- 5 Nov 2026Industrial Redundancy: partialcurrent